Motor Current from Electrical Input Power
Estimate current for a single-phase motor from electrical input power, RMS voltage, and power factor.
01 / INPUTS
Single-phase calculation; power factor must be greater than 0 and at most 1.
02 / RESULT
SINGLE-PHASE CURRENT
5.11508951 A
- Current
- 5.11508951 A
- Power factor
- 0.85
Calculation trace
- 1,000 W ÷ (230 V × 0.85) = 5.11509 A5.11508951 ASingle-phase current
Maintained by Jack Shi
How it works
For single-phase AC, current is I = P ÷ (V × power factor), where P is electrical real input power in watts and V is RMS voltage. Shaft-output power is different: if the shaft rating is known, first divide it by efficiency (as a fraction) to obtain electrical input power. For example, 800 W shaft output at 80% efficiency requires 1000 W electrical input. The calculator does not assume an efficiency.
Assumptions & limits
- Single-phase; you supply the power factor.
- Enter electrical input power at the operating load, not shaft-rated watts. Power factor and efficiency are distinct ratios.
Verified runs
Synthetic examples executed at build revision 24533ff on . Cards round decimal results to 6 significant figures; matching uses full precision and the tolerance below. Matches cover the displayed fields, not every possible input or clinical or engineering validation.
Inputs: Electrical input power: 1000 W electrical input; Voltage: 230 V; Power factor: 0.85 ratio
Result: Current: 5.11509 A (expected Current: 5.1151 A) ✓
Inputs: Electrical input power: 1000 W electrical input; Voltage: 230 V; Power factor: 0 ratio
Result: Rejected: Power factor must be a finite number greater than 0 and at most 1. (expected Rejected) ✓
Inputs: Electrical input power: 746 W electrical input; Voltage: 120 V; Power factor: 1 ratio
Result: Current: 6.21667 A (expected Current: 6.2167 A) ✓
How these runs were checked
Method: motor-current-1ph@1.0.0. Expectations come from the listed test fixtures or hand arithmetic; they are not copied from these executions. Omitted optional inputs use the method defaults. Run dates record execution, not expert review or fresh measurements.
Download all verified runs (JSON) — full inputs, returned values, expectations, timestamps and buildRevision.
- normal: . Absolute tolerance: 0.0005. Text and booleans match exactly. Full-precision result: Current: 5.115089514066496 A. Expected: Current: 5.1151 A. Expectation: packages/calculator-core/tests/motor-current.test.ts
- boundary: . Absolute tolerance: 1e-10. Text and booleans match exactly. Full-precision result: Rejected: Power factor must be a finite number greater than 0 and at most 1.. Expected: Rejected. Expectation: packages/calculator-core/tests/motor-current.test.ts
- sensitivity: . Absolute tolerance: 0.0005. Text and booleans match exactly. Full-precision result: Current: 6.216666666666667 A. Expected: Current: 6.2167 A. Expectation: packages/calculator-core/tests/motor-current.test.ts
Reproduce from the source checkout with pnpm --filter @sumivo/web gen:verified-runs. A rebuild changes execution times; the revision identifies its Git starting point, including any uncommitted changes made for that build.
FAQ
- Does this work for three-phase motors?
- No. Three-phase current uses I = P ÷ (√3 × V × power factor); this tool is single-phase.